Integrated Handheld Welding Laser Water Chiller

Product Overview

1.Manual IntroductionThe 1500-3000W is an air-cooled water chiller that continuously provides cooling water through a compressor refrigeration system, stably supporting full-power long-term laser operation. This product features a compact size, high temperature control accuracy, and simple operation

Update Time:2026-08-21
Traffic:13
Detailed IntroductionOnline Message

微信图片_2026-08-21_165606_598.png

1.Manual Introduction

The 1500-3000W is an air-cooled water chiller that continuously provides cooling water through a compressor refrigeration system, stably supporting full-power long-term laser operation. This product features a compact size, high temperature control accuracy, and simple operation. It can be used to cool heat-generating equipment such as lasers, servers, and motors.


2.Scope of Application

This specification applies to the handheld integrated water chiller units for laser applications, models 1500W, 2000W, and 3000W.


3.Model Series Table

Model seriesMSGA1500wMSGA2000wMSGA3000w
Power Supply220V/50/60Hz220V/50/60Hz220V/50/60Hz
Cooling Capacity1.5kW / 2407kcal/h2.8kW / 3181kcal/h4.1kW / 4815kcal/h
Rated Power1.53kW2.08kW3.54kW
Rated Current7.65A10.4A18A
Pump Power200W370W500W
Pump Flow>10L/min>15L/min>20L/min
Pump Head25m30m35m
Port SizeZG1/2" + ZG1/2"x2ZG3/4" + ZG1/2"x2ZG3/4" + ZG1/2"x2
Control Accuracy±2°C±2°C±2°C
Water Temperature Range15-35°C15-35°C15-35°C
Ambient Temperature-5~45°C-5~45°C-5~45°C
Noise62dB65dB72dB
Protection ClassIP44IP44IP44
Control MethodCapillary throttlingCapillary throttlingCapillary throttling
Tank Volume12L16L16L
Cabinet Dimensions705×320×610mm890×436×690mm1045×520×790mm


4.Product Dimensions

Unit Dimensions

1500w/2000w Integrated Unit

(Images and dimension arrows remain as in original)

  • Front view, rear view, side view with dimensions: 650mm, 370mm, etc.

  • Welding torch holder

  • Actual product photo, right side view

3000w Integrated Unit

  • Front view, right side view, rear view, actual product photo



5.Precautions

  • (This section is empty in the original, but the heading is translated)

    6.Panel Description

  • Display/ControlPurpose
    Digital Display WindowDisplays low‑water measured temperature, low‑water set temperature, high‑water measured temperature, ambient‑temperature‑tracking differential / high‑water differential (when room‑temperature tracking is active it shows "tracking differential"; otherwise it shows "high‑water differential"), ambient temperature (c.xx.x), alarm codes (Exx), and parameter codes (Fxx).
    Indicator Lights
    Unit status (Run)ON: unit working; OFF: unit stopped.
    Normal operation signal (Alarm)ON: no fault; OFF: fault present.
    Refrigeration signal (Refrigeration)ON: compressor running; FLASHING: cooling demand exists but compressor not yet started; OFF: compressor off.
    Heating signal 1 (Heat1)ON: low‑water heating on; OFF: heating off.
    Heating signal 2 (Heat2)ON: low‑water heating on; OFF: heating off.
    Bypass valve (Bypass)ON: bypass valve open; OFF: bypass valve closed.
    Buttons
    Up button (▲)During parameter setting, modifies parameter values.
    Down button (▼)Switches display; during parameter setting, modifies parameter values.
    On/Off button (On/Off)Turns the unit on or off.
    Set button (Set)In non‑fault state, pressing <Set> enters/exits the low‑water set temperature interface.
  • After power‑on, the display shows software version information (F21/003/v100 /Axx) for about 7 seconds, then enters the temperature display state.

  • Temperature Display

  • The PV area shows the measured water temperature; the SV area shows the low‑water set temperature / tracking differential / high‑water differential / ambient temperature.

  • Low‑water interface: PV shows low‑water measured temperature, SV shows low‑water set temperature.

  • High‑water interface: PV shows high‑water measured temperature, SV shows tracking differential / high‑water differential (when room‑temperature tracking is active it shows tracking differential, otherwise high‑water differential).

  • Ambient temperature interface: PV shows ambient temperature, SV shows "c."

  • Press the ▼ button to cycle through low‑water, high‑water, and ambient interfaces. If no operation for 30 seconds, it automatically returns to the low‑water interface.

  • Note: If the ambient temperature probe is not used, the ambient interface is not displayed. "d." is the code for high‑water differential, and xx.x is the temperature value (distinct from tracking differential); "c." is the code for ambient temperature.

  • Fault Display

  • When a fault is detected, the display alternates between the temperature reading and the fault code "Exx". If multiple faults exist, they are cycled automatically. When a fault code is displayed, pressing the <Set> button silences the alarm.

  • Fault codes and descriptions are as follows:

  • Fault CodeFault NameDetection ConditionActionReset
    E01Low‑water probe faultDetected after power‑onAlarm, unit stopManual reset
    E02Low‑water over‑temperature faultDetected after power‑onAlarm, stop low‑water and high‑water electric heatingAuto reset
    E03Compressor faultDetected after [F19 compressor fault detection delay] time from compressor startAlarm, compressor stopAuto reset
    E05Flow alarmDetected after power‑onAlarm, unit stopAuto reset
    E08Low‑water under‑temperature alarmDetected after power‑onAlarm, compressor stopAuto reset
    E09High‑water probe faultDetected after power‑onAlarm, unit stopManual reset
    E10High‑water over‑temperature alarmDetected after power‑onAlarm, stop only high‑water electric heatingAuto reset
    E11High‑water under‑temperature alarmDetected after power‑onAlarm, compressor stopAuto reset
    E12Ambient probe faultDetected after power‑onIn constant‑temperature mode: alarm only, no action; in room‑temperature tracking mode: alarm, unit stopAuto reset
    E13Ambient over‑temperature faultDetected after power‑on; alarm when ambient ≥45°C, auto reset when ≤40°CIn constant‑temperature mode: alarm only, no action; in room‑temperature tracking mode: alarm, stop high‑water electric heatingAuto reset
    E14High‑water flow alarm / other multiplex alarmDetected after power‑onAlarm, unit stopAuto reset
  • Note: For faults requiring manual reset, press the <Set> button to reset the fault; the unit will start automatically once the fault is cleared.